Every PROFIBUS station must have a unique address for communication. These PROFIBUS addresses are coded in one byte and comprise the range 0 - 127. However, individual address values are reserved and no longer free to be assigned.
Address |
Use |
0 |
is reserved as a rule for diagnostic tools, such as programming devices |
1 ... n |
Master station addresses should start with the lowest address. A single master will therefore have address 1.
Additional master stations will have addresses 2, 3... etc. |
n ... 125 |
This means that, in a PROFIBUS network with one master, no more than 124 addresses will be left free for slave stations. |
126 |
is reserved as a delivery address (default) for stations whose address can be adjusted via the bus. This is explained in more detail in the chapter on address changes. |
127 |
is reserved for addressing all or groups (broadcast) and cannot therefore be set for one station. |
Infrastructural components like repeaters, couplers and fibre optic (FO) converters transmit telegrams transparently from one segment to another and therefore do not require their own address.